Basic specifications |
Accuracy guaranteed: 1 year |
Measurement parameters |
• Ground resistance measurement: 4-pole method, 3-pole method, 2-pole method, MEC function, clamp-on measurement (two clamps) • Soil resistivity measurement: 4-pole method • Low-resistance measurement: 4-terminal method, 2-terminal method • Ground potential measurement |
Ground potential |
0 to 30.0 V RMS, accuracy: ±2.3% rdg. ±8 dgt. (50/60 Hz), ±1.3% rdg. ±4 dgt. (DC) |
Functions |
Live wire warning, auto power save, soil resistivity display (4-pole method only), zero-adjustment, auto-hold, continuous measurement mode, wireless communication (only when Z3210 is connected), buzzer sound, comparator, switching the display, ground potential overload display (when measuring ground resistance) |
Operating temperature and humidity |
-25°C to 65°C (*1) (non-condensing) |
Storage temperature and humidity |
-25°C to 65°C: 80% RH or less (non-condensing) |
Dustproof and waterproof |
IP65, IP67 (EN60529) |
Standards |
EN61010 (safety), EN61326 (EMC), EN61557-1/EN61557-10/EN61557-14 (low-resistance measurement, earth testers), EN61557-5 (earth testers) |
Power supply |
HR6 nickel-metal hydride battery x 4 or LR03 alkaline battery × 4 |
Number of measurements per battery charge (*2) |
500 times (3-pole method, without Z3210 installed) 400 times (3-pole method, with Z3210 installed and using wireless communication) |
Dimensions and weight |
Approx. 189 mm (7.44 in.)W × 148 mm (5.83 in.) H × 48 mm (1.89 in.) D, approx. 765 g (26.98 oz.) (including battery, protector) |
Included accessories |
Auxiliary Earthing Rod L9840 (2 piece set) ×2, Measurement Cable L9845-31 ×1, Measurement Cable L9845-33 ×1, Measurement Cable L9845-52 ×1, Measurement Cable L9841 ×1, Test Lead L9787 ×1, Earth Nets Module L9846 ×2, Carrying Case C0208 ×1, Carrying Case C0209 ×1, Protector ×1, LR6 Alkaline battery ×4, Instruction manual ×1, Operating precautions ×1 |